ŁIN

CONNECTOR FOR INSULATION WITH POLYAMIDE STUD
SHORT EXPANSION ZONE

INDEXCONNECTOR LENGTH L [mm]INSULATION MATERIAL
THICKNESS [mm]
QUANTITY [pcs]
ŁIN-0707010-20200
ŁIN-0909030-40200
ŁIN-10010040-50200
ŁIN-12012060-70200
ŁIN-14014080-90200
ŁIN-160160100-110200
ŁIN-180180120-130200
ŁIN-200200140-150200
ŁIN-220220150-170200
ŁIN-260260200-210100
ŁIN-300*300240-250100
ŁIN-350*350290-300100
ŁIN-400*400340-350100

*Available from 2023

SHORT EXPANSION ZONE

TECHNICAL SPECIFICATION:

1) Drill a hole in the wall using a hammer drill and thoroughly remove chips
2) Place the connector in the hole
3) Anchor the connector by hammering the stud
4) Correctly installed insulation connector

CHARACTERISTIC RESISTANCE TO TENSION LOADS NRk IN CONCRETE AND IN MANSORY FOR SINGLE ŁIN ANCHOR

BASEVOLUME DENSITY [ kg / dm³ ]MINIMUM RESISTANCE
TO COMPRESSION
[ N / mm² ]
ACCORDING TO
APPLICABLE
STANDARD
NRk [ kN ]
Concrete C12/15 (use category A)EN 2060,55
Concrete C16/20 to C50/60 (use category A)EN 2060,80
Clay bricks MZ (use category B)≥2,0≥20,0EN 771-11,00
Calcium silicate bricks KS (use category B)≥2,0≥20,0EN 771-20,40
Vertically perforated clay bricks Porotherm 25 P+D (use category C)≥0,8≥15,0EN 771-10,10
Calcium silicate hollow blocks KSL (use category C)≥1,6≥15,0EN 771-20,65
Lightweight concrete blocks LAC (use category D)≥0,88≥5,0EN 771-30,20
Partial safety factor for anchor resistance, ɣM (1)2,0

1) Applicable if no domestic regulations

CORRECT LAYOUT OF CONNECTORS
IN FAÇADE INSULATION

Minimum base thickness - h [mm]100
Minimum connector spacing - smin [mm]100
Minimum distance between the connector and the base - cmin [mm]100